XM31-918-HP
Power Supply
 
 

Alarms
 

Battery
 

Power Supply
Model ALPHA/XM31-918-HP
Firmware V1.04.0
Major Alarm OK
Minor Alarm OK
Operational Mode Line
Charger Mode Float
Tamper Door closed
Power Supply Language English
Power Supply Priority Normal
Input
AC Line Mode OK
Voltage 121.98 V
Current 5.93 A
Power 594 W
Frequency 60 Hz
Tap Status Normal
Frequency Range 3.00 Hz
Current Limit 17.00 A
Input Power Consumption 1,196 Wh
Output
Voltage 86.70 V
Power 474 W
Apparent Power 534.07 VA
Frequency 60.05 Hz
Percent Load 34.20 %
Output Setting 90 V
Output Regulation Fine
Over-current Tolerance 3.000 sec
Retry Delay 60 sec
Retry Limit 20
Active Drop Alarm OK
Active Drop Threshold 50 W
Current 6.16 A
Inverter
Inverter Status Off
End of Discharge Type String
End of Discharge Level 1.75 V/cell
Reduced Peak Mode Disable
Total Standby Events 68
Time Since Last Standby Event 66d 8h:05m
Time in Last Standby Event 0d 0h:42m
Total Time in Standby 1,386 min
Standby Events Since Reset 20
Time in Standby Since Reset 828 min
Time Since Reset 764 day(s)
Total Run Time 764 day(s)
Transformer Run Time 764 day(s)
Total Downtime 0d 0h:07m
Oil Cap Lifespan Consumed 40.2 %
Self Test
Deep Discharge Cycle Timed
Test Countdown 2 day(s)
Test Duration 10 min
Test Interval 30 day(s)
Test Inhibit No

 
Copyright © 2017-2022 EnerSys. All Rights Reserved.