XM31-918-HP
Power Supply
 
 

Alarms
 

Battery
 

Power Supply
Model ALPHA/XM31-918-HP
Firmware V1.04.0
Major Alarm OK
Minor Alarm OK
Operational Mode Line
Charger Mode Float
Tamper Door closed
Power Supply Language English
Power Supply Priority Normal
Input
AC Line Mode OK
Voltage 121.69 V
Current 5.73 A
Power 590 W
Frequency 60 Hz
Tap Status Normal
Frequency Range 3.00 Hz
Current Limit 17.00 A
Input Power Consumption 2,386 Wh
Output
Voltage 87.48 V
Power 472 W
Apparent Power 531.00 VA
Frequency 60.05 Hz
Percent Load 33.70 %
Output Setting 90 V
Output Regulation Fine
Over-current Tolerance 3.000 sec
Retry Delay 60 sec
Retry Limit 20
Active Drop Alarm OK
Active Drop Threshold 50 W
Current 6.07 A
Inverter
Inverter Status Off
End of Discharge Type String
End of Discharge Level 1.75 V/cell
Reduced Peak Mode Disable
Total Standby Events 113
Time Since Last Standby Event 152d 2h:27m
Time in Last Standby Event 0d 0h:01m
Total Time in Standby 1,952 min
Standby Events Since Reset 51
Time in Standby Since Reset 1,254 min
Time Since Reset 1,222 day(s)
Total Run Time 1,222 day(s)
Transformer Run Time 1,222 day(s)
Total Downtime 0d 0h:07m
Oil Cap Lifespan Consumed 61.9 %
Self Test
Deep Discharge Cycle Timed
Test Countdown 29 day(s)
Test Duration 10 min
Test Interval 30 day(s)
Test Inhibit No

 
Copyright © 2017-2022 EnerSys. All Rights Reserved.